Knowledge Base / Rockwell In-chassis / ControlLogix / MVI56 Series / MVI56-AFC

How do I configure a vortex, ultrasonic or coriolis type meter in my AFC module?

Search KB

Kategorien

For Vortex, Ultrasonic or Coriolis meters, the selection depends on the output generated by
the meter.  

If the meter provides a pulse train representing the volume increment, the AFC meter should be
configured as Linear with Primary Input selected as Pulse Count.  

If the meter provides the instantaneous flow rate, then the AFC meter should be configured as
Differential with Primary Input selected as Flow Rate.

 

Related Keywords:

MVI46-AFC, MVI56-AFC, MVI69-AFC, MVI71-AFC, PTQ-AFC, flow