PLX32-EIP-104

EtherNet/IP to IEC 60870-5-104 Gateway

PLX32-EIP-104

Integration of EtherNet/IP products into IEC 60870-5-104 networks can be a challenge, but not with ProSoft Technology’s PLX32-EIP-104 gateway.

The gateway has dual Ethernet ports, providing the option to have one Ethernet port communicating on both EtherNet/IP™ and IEC 60870-5-104 networks, or independent communication ports for each protocol.

The gateway provides powerful communications on EtherNet/IP networks, operating as either a Client or a Server to various devices such as PLC’s, Drives, and various other equipment supporting the EtherNet/IP protocol.

On the IEC 60870-5-104 side of the communications, the gateway operates as a server, accepting commands from client devices such as a SCADA system or DCS system.

Abbildungen

Click on image(s) to enlarge
Drag with the mouse. Click for close.
Drag with the mouse. Click for close.

Funktionen und Vorteile

  • Up to 10,000 words of user-defined memory to share data between IEC 60870-5-104 and EtherNet/IP networks
  • Up to 1000 points of each supported ASDU type can be exchanged on the IEC-60870-5-104 network
  • EtherNet/IP support as both Client (Class 3 PCCC or CIP) and Server (Class 1 I/O, Class 3 PCCC or CIP)
  • Ability to operate using one Ethernet port, or 2 individual Ethernet ports
  • Upload, Download, Diagnostics via ProSoft Configuration Builder (PCB) via an Ethernet connection
  • Configurable Common ASDU address (sector) and Information Object Address for IEC 60870-5-104 application
  • Optional support for SD card for configuration storage (Sold separately)

Technische Daten

EtherNet/IP™ Specifications 

Specification

Description

Number of Class 3 Server Connections

5

Supported Message Types

PCCC and CIP

Number of Class 3 Client Connections

Connected: 2

Unconnected: 1

Number of Class 1 I/O Connections

8

I/O Connection Sizes

248/248

Minimum RPI Time

5mSec per connection

CIP Services Supported

0x4C:CIP Data Table Read
0x4D:CIP Data Table Write
CIP Generic

Command List

Support for 100 commands (Class 3 MSG) per Client

Command Sets

PLC-2/PLC-3/PLC5/SLC500

 

IEC 60870-5-104 Server 

Specification

Description

Operating Mode

IEC 60870-5-104 Server

Simultaneous Connections

3

Unsolicited Messaging

Either cyclic or spontaneous

Group Interrogation

Global, General 1 to 16, Global Counters, Counters 1 to 4

Supported ASDU types

Up to a maximum of 1000 of each of the following ASDU types are supported: M_SP_NA, M_DP_NA, M_ST_NA, M_ME_NA, M_ME_NB, M_ME_NC, M_IT_NA, C_SC_NA, C_DC_NA, C_RC_NA, C_SE_NA, C_SE_NB, C_SE_NC

Hardware-Spezifikationen

Power Supply

24 VDC nominal
10 to 36 VDC allowed
Positive, Negative, GND Terminals

Current Load

24 VDC nominal @ 300 mA
10 to 36 VDC @ 610 mA maximum

Operating Temperature

-25°C to 70°C (-13°F to 158°F)

Storage Temperature

-40°C to 80°C (-40°F to 176°F)

Humidity

IEC 60068-30; 5% to 95%, with no condensation

Shock

IEC 60068-2-27; 15G @ 11ms (Operational)
IEC 60068-2-27; 30G @ 11ms (Non-Operational)

Vibration

IEC 60068-2-6; 5G @ 10 to 150 Hz

Dimensions (H x W x D)

5.38 x 1.99 x 4.38 in
13.67 x 5.05 x 11.13 cm

Ethernet Port

(2) 10/100 Base-T, RJ45 connector

SD Card

(Optional) Maximum supported size 32GB (located at back of gateway)

Zertifikate

ATEX Letter of Conformity 107,32 kB Zuletzt geändert 12.05.2022
CB Safety 348,30 kB Zuletzt geändert 20.10.2022
Korean KC Registration 974,32 kB Zuletzt geändert 07.07.2020
UL Certificate of Compliance 233,35 kB Zuletzt geändert 16.11.2022
Country Approval - Australia 192,66 kB Zuletzt geändert 07.10.2020
Country Approval - Eurasian Customs Union Conformity (EAC) (Wired) 1,92 MB Zuletzt geändert 10.07.2020
Declaration of Conformity (RoHS/CE) 114,24 kB Zuletzt geändert 01.06.2022
Declaration of REACH Compliance 145,49 kB Zuletzt geändert 01.06.2022