      MVI56E-FLN

      FA Control Network Enhanced Communication Module

      MVI56E-FLN

      The MVI56E-FLN FA Control Network Enhanced communication module is a single-slot solution that allows ControlLogix-compatible processors to easily interface with other FL-net protocol devices. The module is certified for use with FL-net version 2.00 (OPCN-2) for the standard FA control network, as defined by JEMA (The Japan Electrical Manufacturers Association).

      The MVI56E-FLN module acts as a gateway between the FL-net network and the ControlLogix backplane. The data transfer from the ControlLogix processor is asynchronous from the actions on the FL-net network.

      The MVI56E-FLN module accepts commands to control and monitor the data stored in its databases. This data is passed between the module and the ControlLogix processor over the backplane for automation and control applications.

      • Funktionen und Vorteile
      • Technische Daten
      • Hardware-Spezifikationen
      • Downloads
      • Videos
      • Zertifikate

      Funktionen und Vorteile

      RSLogix 5000 Integrated

      • Module configuration and communication is integrated within RSLogix 5000
      • No additional programming or configuration software is required

      Personality Module

      • Incorporates a non-volatile Compact Flash memory for storing the module's setup and network configuration data (or personality).
      • Allows restoring of a module by simply exchanging the Personality Module (for disaster recovery), without the need to use a PC or re-configure.

      Ethernet Port with Built-in Web Server

      • Module Ethernet port provides a built-in web server for access to module status and to update the module firmware.
      • Local and remote diagnostics access available through the Ethernet port

      Technische Daten

      General Specifications

      • Single-slot, 1756 backplane-compatible
      • The module appears as an Input/Output module to the ControlLogix® (CLX) processor
      • Ladder logic is used for data transfer between module and processor (sample ladder file included on CD)
      • Can be installed in Local or Remote CLX racks

      Functional Specifications MVI56E-FLN

      • Message Transfer Command functions
        • Log data read service (server function)
        • Log data clear service (server function)
        • Network Parameter Read (server function)
        • Return Message (server function)
        • Profile Read (server function)
        • Network Management Table: According to FL-net version 2.00 specification
        • Own-node Management Table: According to FL-net version 2.00 specification
        • Participating Node Management Table: According to FL-net version 2.00 specification
        • Maximum 249 nodes of user data
      • Discovery service: Allows ProSoft Configuration Builder (or separate utility) to find and display products located on the network with key product attributes such as name, serial number, and IP address.
      • LED Display: LED provides detailed, plain English diagnostics and error information for the module, backplane communication, and network conditions.
      • Master-less token control method.
      • FA link protocol on Ethernet UDP/IP
      • Cyclic data transfer: Supports virtual memory Area 1 (512 words) and Area 2 (8192 words). The cyclic data is mapped to the modules I/O area.
      • Configurable Mapping Feature: Optimization of Input Data mapping from the network
      • Configurable Minimum Frame Interval Time (0 to 50 with each unit being equal to 100 Ms)
      • Configurable Token Watchdog Time (1 Ms to 255 Ms)

      Hardware-Spezifikationen

      Specification

      Description

      Backplane Current Load

      mA @ 5 Vdc 

      mA @ 24 Vdc

      Operating Temperature

      32° F to 140°F (0° C to 60°C)

      Storage Temperature

      -40° F to 185°F (-40° C to 85°C)

      Shock

      30g Operational

      50g non-operational

      Vibration: 5g from 10 Hz to 150 Hz

      Baud Rate

      10/100 Mbit/s

      Relative Humidity

      5% to 95% RH,  with no condensation

      LED Indicators

      Module Status (OK)

      Application Status(APP)

      ERR (not used)

      Ethernet Ports 

       

      Ethernet Port 1(E1)

      Configuration only

      10/100 Base-T

      RJ45 Connector

      Link and activity LED indicators

      Electrical Isolation 1500 V rms at 50 Hz to 60 Hz

      for 60 s, applied as specified in section 5.3.2 of

      IEC 60950: 1991

      Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration

      Ethernet Port 2 (E2)

      FL-net Application Only

      10/100 Base-T

      RJ45 Connector

      Link and activity LED indicators

      Electrical Isolation 1500 V rms at 50 Hz to 60 Hz

      for 60 s, applied as specified in section 5.3.2 of

      IEC 60950: 1991

      Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration

      Downloads

      MVI56E-FLN Datasheet 429,73 kB Zuletzt geändert 09.12.2022
      MVI56E-FLN User Manual 2,76 MB Zuletzt geändert 23.10.2025
      MVI56E FLN Ladder 456,52 kB Zuletzt geändert 19.09.2012
      ProSoft Configuration Builder
      MVI56E-FLN EDS File 1,12 kB Zuletzt geändert 20.12.2018
      MVI56E CAD Drawings (STEP) 11,16 MB Zuletzt geändert 15.09.2023
      LifeCycle Letter MVI56E Series 150,72 kB Zuletzt geändert 01.04.2026

      Videos

      Data Organization in ProSoft Modules and Gateways

      Guide to bit-level data addressing in ProSoft Modbus modules

      Guide to 32-bit data types in ProSoft Modbus modules

      Zertifikate

      CB Safety 504,75 kB Zuletzt geändert 06.10.2021
      Country Approval - Eurasian Customs Union Conformity (EAC) (Wired) 1,92 MB Zuletzt geändert 10.07.2020
      IECEx 162,02 kB Zuletzt geändert 25.05.2016
      JEMA Certification 410,12 kB Zuletzt geändert 25.05.2016
      Korean KC Registration 185,94 kB Zuletzt geändert 11.09.2020
      Declaration of Conformity (RoHS/CE) 136,60 kB Zuletzt geändert 20.01.2023
      ATEX Letter of Conformity 101,65 kB Zuletzt geändert 12.05.2022
      UL CoC 83,45 kB Zuletzt geändert 23.06.2020
      Declaration of REACH Compliance 388,80 kB Zuletzt geändert 18.12.2025

Solutions

  • Amusement
  • Automated Material Handling
  • Automotive
  • IIoT Solutions
  • Mining and Metals
  • Modernization
  • Oil and Gas Solutions
  • Secure Remote Connectivity
  • Water & Wastewater

Produkte

  • Fernzugriff
  • Rockwell Automation In-chassis
  • Gateways
  • Industrial Wireless
  • ProSoft-Software

Service & Support

  • Knowledge Base
  • Regionaler technischer Support
  • Legacy Downloads
  • Training
  • $(document).ready(function(){ $('.popup-youtube, .popup-vimeo, .popup-gmaps').magnificPopup({ disableOn: 700, type: 'iframe', mainClass: 'mfp-fade', removalDelay: 160, preloader: false, fixedContentPos: false }); //pagelayout banner? if($('.banner-image') !== 'undefined' ){ var banner_image_src = $('.banner-image img').attr('src'); $('.banner-image').hide(); $('.banner-page-title').css('background-image', 'url(' + banner_image_src + ')'); $('.banner-page-title').css('background-repeat', 'no-repeat'); } //if( $('.analytics-file-download' ) !== 'undefined' ) { // $('.analytics-file-download' ).click(function(){ // var action = $( this ).attr( 'href' ); // var label = $( this ).attr( '_gaq-label' ); // var category = $( this ).attr( '_gaq-category' ); // return ga('send', 'event', category, action, label); // }); //} //initialize search? $("#div_search_field input").focusin(function(){ $(this).css("color", "#000000"); }); var initialSearch = $('form.search input.text').attr("value"); var currentSearch = ""; $('form.search input.text').focusin(function(){ currentSearch = $('form.search input.text').attr("value"); if( currentSearch == initialSearch ) { $('form.search input.text').attr("value",""); } }); }); //Homepage slideshow if( $('#slider') !== 'undefined' ) { $('#slider').nivoSlider({ pauseTime: 7000 // time for a slide to show, in milliseconds; subtract 2 seconds for actual time due to transition time }); } //eZ Live Viewer //(function(){var ff=document.createElement('script');ff.type='text/javascript';ff.async=true;ff.src=('https:'==document.location.protocol?'https':'http')+'://liveviewer.ez.no/statjs/sst-118-973155090/stat.js';var s=document.getElementsByTagName('script')[0];s.parentNode.insertBefore(ff,s);})(); // Pardot integration piAId = '281892'; piCId = '1546'; (function() { function async_load(){ var s = document.createElement('script'); s.type = 'text/javascript'; s.src = ('https:' == document.location.protocol ? 'https://pi' : 'http://cdn') + '.pardot.com/pd.js'; var c = document.getElementsByTagName('script')[0]; c.parentNode.insertBefore(s, c); } if(window.attachEvent) { window.attachEvent('onload', async_load); } else { window.addEventListener('load', async_load, false); } })();