The MVI56E-MCMR Enhanced Modbus Master/Slave Communication Module with Reduced Data Block allows Rockwell Automation® ControlLogix® processors to easily interface with devices using the Modbus RTU/ASCII serial communications protocol. Compatible devices include a wide variety of instruments, process measurement devices, popular brands of programmable logic controllers (PLCs) and programmable automation controllers (PACs).
The MVI56E-MCMR acts as an input/output module on the ControlLogix backplane, making Modbus data appear as I/O data to the processor. Backplane data transfers to and from the processor are asynchronous from communications on the Modbus network. Two independently-configurable serial ports can operate on the same or different Modbus networks. Each port can be configured as a Modbus Master or Slave, sharing the same user-controlled 5000-word database.
The MVI56E-MCMR utilizes a reduced Input/Output (I/O) data block for transferring data to and from a ControlLogix processor. This reduced data block makes it ideal for use in remote rack applications over ControlNet™. For EtherNet/IP™ applications where bandwidth is not an issue, it is strongly recommended to use the MVI56E- MCM.
Features |
Benefits |
Backward Compatibility |
|
Reduced Data Block |
|
CIPconnect-enabled |
|
4-digit LED display |
|
ProSoft Configuration Builder (PCB) provides a graphical configuration tool for quick and easy management of module configuration files, as well as viewing communication and module diagnostic information.
CIPconnect technology routes connections over multiple EtherNet/IP or ControlNet paths, allowing you to manage the module from remote locations.
The MVI56E-MCMR Setup Guide, with the sample configuration, provides step-by-step instructions on how to move data through the module from the network to the processor.
Communication Parameters |
Baud Rate: 110 baud to 115.2 kbps Stop Bits: 1 or 2 Data Size: 7 or 8 bits Parity: None, Even, Odd RTS Timing delays: 0 to 65535 milliseconds |
Modbus Modes |
RTU mode (binary) with CRC-16 ASCII mode with LRC error checking |
Floating Point Data |
Floating point data movement supported, including configurable support for Enron and Daniel implementations |
Modbus Function Codes |
1: Read Coils Status 2: Read Input Status 3: Read Holding Registers 4: Read Input Registers 5: Force (Write) Single Coil 6: Preset (Write) Single Register 8: Diagnostics 15: Force (Write) Multiple Coils 16: Preset (Write) Multiple Data Registers 17: Report Slave ID 22: Mask Write 4x Register 23: Read/Write 4x Registers |
Specification |
Description |
Backplane Current Load |
800 mA @ 5 V DC3 mA @ 24 Vdc |
Operating Temperature |
0°C to 60°C (32°F to 140°F) - MVI56E-MCM |
Storage Temperature |
-40°C to 85°C (-40°F to 185°F) |
Shock: |
30g Operational |
Relative Humidity |
5 to 95% (without condensing) |
LED Indicators |
Battery Status (ERR) Application Status (APP) Module Status (OK) |
4-Character, Scrolling, Alpha-Numeric LED Display |
Shows Module, Version, IP, Port Master/SlaveSetting, Port Status, and Error Information |
Debug/Configuration Ethernet port (E1 - Config) |
|
Ethernet Port |
10/100 Base-T, RJ45 Connector, for CAT5 cable Link and Activity LED indicators Auto-crossover cable detection |
Serial Application ports (P1 & P2) Full hardware handshaking control, providing radio, modem, and multi-drop support |
|
Software configurable communication parameters |
Baud rate: 110 baud to 115.2kbps RS-232, 485 and 422 Parity: none, odd or even Data bits: 5, 6, 7, 8 Stop bits: 1 or 2 RTS on/off delay: 0 to 65535 milliseconds |
Serial Applications Ports (P1, P2) |
RJ45 (DB-9M with supplied adapter cable) Configurable RS-232 hardware handshaking 500V Optical isolation from backplane RS-232, RS-422, RS-485 jumper-select, each port RX (Receive) and TX (Transmit) LEDs, each port |
Shipped with Unit |
RJ45 to DB-9M cables for each serial port 5 foot Ethernet Straight-Thru Cable (Gray) |
CB Safety | 504,75 kB | Zuletzt geändert 06.10.2021 |
Country Approval - Eurasian Customs Union Conformity (EAC) (Wired) | 1,92 MB | Zuletzt geändert 10.07.2020 |
IECEx | 162,02 kB | Zuletzt geändert 25.05.2016 |
Declaration of Conformity (RoHS/CE) | 136,60 kB | Zuletzt geändert 20.01.2023 |
ATEX Letter of Conformity | 101,65 kB | Zuletzt geändert 12.05.2022 |
UL CoC | 83,45 kB | Zuletzt geändert 23.06.2020 |
Korean KC Registration | 586,65 kB | Zuletzt geändert 11.09.2020 |
Declaration of REACH Compliance | 134,07 kB | Zuletzt geändert 20.05.2022 |