AN-X3-PB gateway

PROFIBUS DP Multi-Slave Ethernet HMI or UDP Gateway Non-CE

AN-X3-PB

The AN-X3-PB acts as a gateway between a PROFIBUS DP network and an Ethernet network. The gateway allows the mapping of PROFIBUS DP I/O data to an EtherNet/IP™ controller or Modbus® TCP Client. The AN-X3-PB can connect a PC or other device to a PROFIBUS network. The gateway has a web interface for configuring the PROFIBUS and Ethernet properties.

Abbildungen

Click on image(s) to enlarge
Drag with the mouse. Click for close.
Drag with the mouse. Click for close.

Funktionen und Vorteile

  •        Configures through a web browser (No special configuration software required)
  •        Customizable configuration files provide additional flexibility
  •        Supports offline configuration through a .CSV file
  •        View diagnostics with a web browser for remote monitoring and troubleshooting

Anwendungen

HMI

The AN-X3-PB gateway running the HMI firmware acts like a gateway between a PROFIBUS DP network and an Ethernet network supporting EtherNet/IP scheduled connections, PLC5 file emulation, and Modbus TCP.

  • Scheduled Connection size 250/248 (input/output)
  • PROFIBUS DP I/O can be mapped to the scheduled connections
  • PLC5 File emulation allows users to map PROFIBUS DP I/O data to N or F type files
  • Map PROFIBUS DP I/O data to Modbus registers using Modbus TCP Server functionality

UDP

The AN-X3-PB acts as a gateway between a PROFIBUS DP network and an Ethernet network using cyclic UDP messages.         

  • Supports up to 16 UDP send blocks and up to 16 UDP receive blocks
  • Each block supports a standard frame size (MTU) of up to 1500 bytes
  • With Ethernet, IP, UDP and QTS overhead, there are 1448 bytes or 362 DWORDS (32 bits) available to map PROFIBUS diagnostics and data
  • Both Unicast and Multicast frames are supported

Technische Daten

EtherNet/IP Support

Scheduled Connections

  • Data Types: INT, DINT, Real
  • Connection size 250/248 (input/output)
  • Configurable RPI time for each connection (1 to 750ms)
  • PROFIBUS DP I/O data can be mapped to the scheduled connections
  • EtherNet/IP Class 1
  • Number of connections: 16

Unscheduled PLC-5 Emulation

  • Allows users to access PROFIBUS DP data on an Ethernet network
  • PROFIBUS DP I/O data can be mapped to N and F type PLC-5 files

 

Modbus® TCP Support

  • Modbus TCP Server allows users to map PROFIBUS DP I/O data to Modbus registers

 

PROFIBUS DP Support

  • Acts as one or more active PROFIBUS DP slave nodes, up to 125 total
  • Monitors the I/O data from all other PROFIBUS DP slave nodes on the PROFIBUS network
  • Maintains PROFIBUS DP slave node list
  • Maintains PROFIBUS diagnostic counters
  • Supports baud rates of 9600bps to 12Mbps

Hardware-Spezifikationen

Hardware Specifications

Specification

Description

Maximum Power Consumption

160 mA at 12 VDC, 80 mA at 24 VDC

Maximum Power dissipation

2 Watts

Operational Temperature

0°C to 50°C (32°F to 122°F)

Storage Temperature

-40°C to 85°C (-40°F to 185°F)

Relative Humidity

5% to 85% without condensation

 

Hardware Features

  • Ethernet RJ45 connector
  • 9-pin D Shell connector to connect to the PROFIBUS network
  • 3-pin Phoenix power connector
  • microSD card for storage of configuration data and firmware