In the configuration of the GOOSE message for the IEC-61850 protocol on a GE relay, it is necessary to configure the GOOSE message to go to the GOOSE MAC address, rather than the actual MAC address of the relay. Attached is a screen capture showing the configuration scr...
Erfahren Sie mehrWhen using a .ICD file to configure devices on an IEC 61850 network there are potential issues in importing the file into the 61850 Configuration Manager software. There are a couple of things to look at. 1) The configuration tool ac...
Erfahren Sie mehrIf MMS reports are not working with a ProSoft IEC 61850 client gateway please review the following points, as the most common reasons are listed below:1.Mismatch between the IEC 61850 client and server configuration: verify that the report configuration loaded in the Server and t...
Erfahren Sie mehrYes, the Ethernet port(s) will work with either cross-over cables or standard Ethernet patch cables to a switch or another device....
Erfahren Sie mehrMost ProSoft products which either go in a Rockwell PLC rack (InRAx modules) or communicate over EtherNet/IP (EIP), most of these products do not require an .EDS file for proper operation. Because of this. we do not provide .EDS files for every product which could support them. ...
Erfahren Sie mehr