The PDPMV1 operating state is stored in the MVIxxPDPMV1.Status.Fieldbus.FB_op_state tag: 00 = Offline 40 = Stop 80 = Clear C0 = OperateTo determine slave status, the MVIxxPDPMV1.Status.Fieldbus.FB_Slave_Data_xfer array contains a bitmap of all the PROFIBUS ...
Erfahren Sie mehrThe attached file shows how to set up a S7-315 CPU to be a PROFIBUS DP Slave to a ProSoft MVI56-PDPMV1 PROFIBUS Master and was written for that specific application. However, many of the setup steps apply to other S7 configurations and other ProSoft PROFIBUS Masters.Please see th...
Erfahren Sie mehrRegistration number : F70FF09BF806Related Keywords:Sycon software all PDPM ProLinx modules (pdpm - profibus dp master protocol)...
Erfahren Sie mehrThe data movement in the PROFIBUS Slave module (PDPS) is as follows: Input registers (0 - 99) move from the PROFIBUS Slave module to the PROFIBUS Master. Output registers (100 - 199) move from the PROFIBUS Master to the PROFIBUS Slave module. With the PROFIBUS protocol, input and...
Erfahren Sie mehrPlease click on the attachment for a tech note on this protocol....
Erfahren Sie mehrBy itself the module does not support PROFIBUS PA. However, when used with a PROFIBUS DP/PA coupler, it is possible to communicate with the ProLinx module via PROFIBUS PA.Related Keywords:PROFIBUS PA DP PDPS PDPM...
Erfahren Sie mehrMake sure to drop the "3170-PDP 1.2 status" information into the first slot, then each of your I/O modules after that. Any unused slots must have a "flex I/O empty slot" defined in the configuration for that slot setup....
Erfahren Sie mehrNot all PROFIBUS DP v1 Master devices support Master to Master or "peer-to peer" messaging, as some do. ProSoft PROFIBUS DP v1 Master solutions (those with -PDPMV1 in their part numbers) do not have peer-to-peer support built-in. However, a PDPMV1 ...
Erfahren Sie mehrSorry; but this is not possible. However, a ProSoft PROFIBUS DP v1 Master can be configured to pass data to and from another PROFIBUS DP Master by using a third-party DP-to-DP coupler....
Erfahren Sie mehrPlease do not use the "Online - Download Configuration" menu option from inside the PCB "PROFIBUS - PDPMV1" configuration window. If you do this, it will lock up PCB, requiring you to shut it down and restart it to clear the error.Instead, exit the "...
Erfahren Sie mehrMany things can result in these symptoms. One of the most common causes is that not all slave manufacturers use a standard byte order. It is very possible that when you think you're sending a value of "1" to a slave's bit address 0, you may be...
Erfahren Sie mehrPROFIBUS DP GSD file names should be limited to eight characters. File names longer than eight characters will cause this error.Delete the excess characters in the file name so that the file name contains no more than eight characters before the .gsd extension.Related Keywords:P...
Erfahren Sie mehrThe question has several possible answers. Most of them are obvious to anyone familiar with PROFIBUS networks, so we won't mention them all here.However, there is one remote possibility that has been known to cause problems in the past that might bear checking. The pa...
Erfahren Sie mehrDue to GSD file errors or device configuration errrors the module may not be able to go into RUN mode. However depending on the type of error (invalid GSD file or exceeding parameter data configuration) the ProSoft Configuration Builder software&nbs...
Erfahren Sie mehrThe PS69-DPM does not communicate natively at 45.45 baud.To communicate through this DP/PA coupler you will need theSiemens Simatic DP Link....