A conditional command is useful when the same value does not need to be written to the end device continuously, but rather on change. A conditional write command is scanned based upon its poll rate (like all other commands). The difference is that it will not be execut...
Erfahren Sie mehrSince RSLogix uses signed integers, the highest positive value that can be entered is 32767. To avoid this issue, when specifying higher baud rates, Prosoftmodules only require the first 3 digits of the baud rate. e.g., to enter a baud rate of 38400, enter 384. Use 576 for 5...
Erfahren Sie mehrOn bottom of the circuit board for any MVI products, you' ll find three jumper banks: COM1, COM2, and Setup.Each jumper position is labeled 232, 422 and 485....
Erfahren Sie mehrThe two application serial ports provide 1000 volts of electrical isolation between the port and the ControlLogix backplane.The debug/configuration port provides no electrical isolation. Note: None of the ports provide any electrical isolation between the port and the module's i...
Erfahren Sie mehrThis is a known issue with Allen Bradley and AB Technote #67950 has been created. "There is an anomaly with all Logix processors in V17 and V18 in which the serial port UART may stall when transmitting packets. This has only appeared on certain devices connec...