Knowledge Base / Rockwell In-chassis / ControlLogix / MVI56 Series / MVI56-AFC

Using AFC modules with corrected (net) flow as in input

Search KB

Kategorien

The AFC is not designed to receive a corrected flow input.

However if the AFC is being used only for its accumulation and archive capabilities, then rather than the process temperature and pressure inputs, provide the meter's reference conditions as the AFC's temperature and pressure inputs.

Typically 15C and 101.325kPa (SI) or 60F and 14.73 PSIA (US).